0700 0700 SUBMENU OUTPUTS

0705

0705 ANALOG OUT1

Output Frequency

Analogue output 1

Analogue output 0 – 10V = 0 - 100%

Terminal:

X3/20

Possible settings: - Actual value

- Output frequency (0 - fmax)

0710

0710 ANALOG OUT2

Actual value

Analogue output 2

Possible settings:

Actual Value, Output frequency

Analogue output 4 – 20mA = 0 - 100%

Terminal: X3/21

Possible settings: - Actual value

- Output frequency (0 - fmax)

0715

0715 CONF REL 1

Running

Configuration of the status relay 1 (X5/1-2-3)

0720

0720 CONF. REL 2

Errors

Configuration of the status relay 2 (X5/4-5-6)

Possible settings: Power, Errors, Warnings, StandBy, Errorreset, Errors of BASICs,

Warnings+BASICs

config.

explanation of status

Action if status=YES

Power

HYDROVAR is connected to power supply

Relay 1: X5/ 1-3 closed
Relay 2: X5/ 4-6 closed

Running

Motor is running

Relay 1: X5/ 1-3 closed
Relay 2: X5/ 4-6 closed

Errors

An error is indicated on the HYDROVAR

(incl. power failure)

Relay 1: X5/ 1-2 closed
Relay 2: X5/ 4-5 closed

Warnings

A warning is indicated on the HYDROVAR

Relay 1: X5/ 1-2 closed
Relay 2: X5/ 4-5 closed

StandBy

Pump is released manually and by external release, no

error/warning is indicated and HYDROVAR doesn’t run

Relay 1: X5/ 1-3 closed
Relay 2: X5/ 4-6 closed

Errorreset

If Parameter ERRORRESET [0615] is activated and a

Warning occurs 5 times -> Error ->

Relay 1: X5/ 1-3 closed
Relay 2: X5/ 4-6 closed

Error of

BASICs

A failure is indicated at least on one BASIC

Relay 1: X5/ 1-2 closed
Relay 2: X5/ 4-5 closed

Warnings

+ BASICs

A warning is indicated on the HYDROVAR or at least

on one BASIC

Relay 1: X5/ 1-2 closed
Relay 2: X5/ 4-5 closed