Cpm menu 19, Cpm menu notes: 19, Cpm menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 109

Advertising
background image

CPM Setup

Page

19 - 1

19

19

Cathodic Protection Monitor (CPM)
SETUP PROGRAMMING

CPM Menu

Remember:

The TS-CPM is programmed from the CPM
menu, which is under Setup. To reach this
menu, press the

Menu

key>

M1

then the

Down

t key until CPM is displayed.

Press the menu key (

M1

thru

M4

) that is below

the text: CPM. Two sub-menus are shown
under the Cathodic Protection Menu. Press

M1

to access the DATA menu and

M2

for the

ALARM menu.

Push

M1

under the DATA menu and select

ENABLE. Then select YES under the CPM
ENABLE menu, only when a CPM unit is/will be
attached to the Tank Sentinel tank gauge.
Press

M2

under the ALARM menu and select

AMPS.

CPM Menu Notes:

1) Before programming, reference the State and

Local Regulations about the interval of Cathodic
Protection Monitoring / Survey Reporting and
requirements.

2) Enter 80% of the output amperage level that

was documented on the last UST 3-6 Month(ly)
Survey Report and use this value as the current
limit (amp) alarm setpoint.

For Example: 80% of 4.2 amps = 3.36 (used for
the current alarm set-point)

Contents:
CPM Menu
Worksheet #19-1
Output Groups -
Line Leak Tests

See the Table of Contents to find topics in
this manual. See the Preface for general
information about this manual. And see the
Installation, Operator’s, TroubleShooting
Guides, and Application Notes for other
reference material.

SELECT MENU OPTION

(MORE)

S E T U P

UPGRADE LANGUAGE

DATALOG

M1

M2

M3

M4

Press the

DOWN

key two or three times ...

SETUP MENU

(MORE)

EXIT

SYSTEM

TANKS

PROBES

H

U

MENU

×

Press this key and follow the

7

highlighted sequence below

CONTINUED

ON

NEXT

PAGE

CATHODIC PROTECTION

D ATA

ALARM

M1

M2

M3

M4

SETUP MENU

(MORE)

TS-ROM

SENSORS AUX INPUT

C P M

M1

M2

M3

M4