Scald (tank leak) test menu 11, Scald (tank leak) test menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 75

Advertising
background image

11

Page

11- 2

Tank Sentinel Setup Programming Guide

SCALD (tank leak) Test Menu

N = Tanks 1 – 8

(only the NO. of TANKS

SCALD TESTS

programmed in the System menu will appear)

CONFIDNCE

SCALD CONFIDENCE

99.0%

Keep the default 99.0% value

90.0%
95.0%
97.5%

Press

ENTER

to accept this data.

PRECISION

SCALD TEST PRECISION

+0.2

Keep the default 0.2 gph monthly test value
Press

ENTER

to accept this data.

INTERVAL

SCALD INTERVAL

18

Keep the default value (18)
Press

ENTER

to accept this data.

QUALIFY

(minimum volume percent before starting a test)

SCALD VOLUME QUALIFY

+0

0.0 to 99.0%

Use keypad to input a percentage.
Press

ENTER

to accept this data.

Reference Local codes (and/or State / Province /
Federal codes) for the minimum percentage of
tank-volume-capacity before a leak test results
can, or will, be considered acceptable. Input the
minimum-acceptable volume based on these
regulations.

ENABLE

(select tanks to be SCALD leak tested)

SCALD ENABLE

Keep the default – all tanks ENABLED

TANK 1
TANK 2

Use

UP/DOWN

keys to show more choices.

:

TANK 8

Press the (

M

) key to select a TANK #.

SCALD ENABLE

ENABLED

Use

UP/DOWN

keys to change the setting.

DISABLED

Press

ENTER

to accept this data.

Press the

CANCEL

key to return to the SCALD TESTS menus.

— C

ONTINUED

ON

NEXT

PAGE

Monthly

Compliance

Yearly Test

SCALD Leak Test:

0.2 gph

0.1 gph

Precision:

Threshold = 1/2 of Leak Test value

NOTE