TS-TPI Setup Programming

Page

23 - 7

23

PUMP N Menu

continued —

HEIGHT

(user entry)

Here is the PUMP N menu, showing TANK
and HEIGHT menus....

Press the

M2

key to display the HEIGHT

PUMP N user entry field ....

The default HEIGHT of ‘+7.0’ (inches) is
displayed ....

Press the

M4

key to backspace and erase

the ‘+7.00000’ default height number.

Use the keypad to enter the height value.

Press the

ENTER

key to accept data entry.

The display returns to the PUMP N menu
showing TANK and HEIGHT.

To repeat these steps for the next pump:

• Press the CANCEL key to display the TPI PUMP menu, which displays AUTO CFG, PUMP 1,
PUMP 2 ....

• Repeat each Pump N Menu step for every PUMP number.

When these entries are completed ....

• Press the CANCEL key to display the main TPI menu, which displays ENABLE, PUMP and
GROUP.

— Proceed to the next menu - TPI Group

PUMP N

(MORE)

TA N K

H E I G H T

M1

M2

M3

M4

HEIGHT PUMP 1

NUMERIC

+7.00

BACKSPACE

M1

M2

M3

M4

The value is the distance (in inches or
centimeters) between the bottom of the PUMP
to the bottom of the TANK. This allows the
pump height to be set by the user, which affects
the handling of the DRY TANK, BLOCKED
INTAKE, and PUMP IN WATER alarms. This
variable defaults to 7 inches and is user-
programmable. The range allowed is 0 to 65.