Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual
Page 87
Annunciator Setup
Page
14 - 3
14
INCON Recommends that you program one of the
annunciators to react to system fail warnings and any leak
detection sensors and leak test fail alarms
.
• Test the Modulated ALARM HORN ANNUNCIATOR
Go back to the ANNUNCIATORS menu and push the
M3
menu key (under TEST) to activate the horn. The horn will
stop when the modulated annunciator timeout value is
reached – or – when any other key is pressed.
• Test the Solid ALARM HORN ANNUNCIATOR
The solid alarm horn annunciator can be tested from the front
panel by exiting SETUP and pressing the ALARM TEST key
(only in the normal Run Mode).
The horn will stop when the
solid annunciator timeout value is reached – or – when any
other key is pressed.
— Your Notes —
—
❖
—
NOTE
☞
NOTE
☞
Annunciator Testing
TEST
HIT ANY KEY TO QUIT