Tanks – special tank n menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 29

Advertising
background image

2

Page

2 - 6

Tank Sentinel Setup Programming Guide

Tanks – SPECIAL TANK N Menu

(C

ONTINUED

)

SPECIAL TANK N

N refers to / represents a tank number

COPY

Press the

M1

key.

COPY FROM SPECIAL TANK X TO N

Select a tank to copy data from (use

M

key).

SPECIAL 1

COPY SPECIAL TANK N TO N
PRESS ENTER IF YOU ARE SURE?

Press

ENTER

to accept this data.

Use

UP

/

DOWN

▲▼

keys to display tanks 5-8.

DIAMETER

Press the

M2

key.

TANK DIAMETER N

+96.00

0.0 to 999,999

Use the

M4

key to use BACKSPACE.

Use the Keypad to input the special tank diameter.
Press

ENTER

to accept this data.

LENGTH

Press the

M3

key.

TANK LENGTH N

+324.000

0.0 to 999,999

Use the

M4

key to use BACKSPACE.

Use the Keypad to input the special tank diameter.
Press

ENTER

to accept this data. (Correction points

can be added between inaccurate level positions.)

(HEIGHT will replace LENGTH when VERTICAL is selected as the TANK DATA SHAPE)

HEIGHT

Press the

M3

key.

TANK HEIGHT N

+324.000

0.0 to 1999.0

Use the

M4

key to use BACKSPACE.

Use the Keypad to input the special tank diameter.
Press

ENTER

to accept this data.

CORR TABL

Press the

M4

key.

CORRECTION TABLE N

(Position (POS #) ...see

NOTES

in this section)

ADD

Press the

M1

key. POS 1 is the lowest value tank.

Two values (LEVEL and VOLUME) are required.

LEVEL

+0

Use the Keypad to input level of strapping point.

Press

ENTER

to accept this data.

VOLUME

+0

Use the Keypad to input volume at that level point.

Press

ENTER

to accept this data.

NOTE