Manifolds alarms menu 6, Manifolds data menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 47

Advertising
background image

6

Page

6 - 2

Tank Sentinel Setup Programming Guide

Manifolds Data Menu

(C

ONTINUED

...

FROM

PREVIOUS

PAGE

)

NAME

Press

M2

key.

MANIFOLD NAME N
MAN N

9 characters

Use keypad to input a name for the Manifold.
Press

ENTER

to accept this data.

PRODUCT

Press

M3

key.

PRODUCT FOR MANIFOLD N

PRODUCT 1

Press

UP/DOWN

to select a product #.

:

PRODUCT 8

Press

ENTER

to accept this data.

( If tanks are set to manifold, then the product
section of the tank menu disappears )

DEL THRES

Press

M4

key.

DELIVERY THRESHOLD N
+200.000

1 to 99999.0

Use keypad to input value in volume units...
per total capacity.
Press

ENTER

to accept this data.

Manifolds ALARMS Menu

Use this menu to input the Manifold Product Volume
Limits (optional). Access the ALARMS menu; go back to
the parent menu and then choose ALARMS ( press

M2

).

ALARMS

Press

M2

key.

MANIFOLD ALARMS MANIFOLD

MAN 1

Press the (

M

) key to select the MAN# for alarm setup.

:

(Manifold # 3 and 4 are for TS-2001/508 only)

MAN 4

COPY

(Optional - used to copy alarm data) Press

M1

key.

COPY MANIFOLD ALARMS X TO N

Press (

M

) key to select MAN# to copy alarm data from.

MAN 1

:

MAN 4

COPY MANIFOLD ALARMS X TO N
PRESS ENTER IF YOU ARE SURE?

Press

ENTER

to accept this data.

LOW LIM

Press

M2

key.

LOW PRODUCT VOLUME LIMIT N

+0

0 to 50000.0

Use keypad to input alarm limits.
Press

ENTER

to accept this data.

L LIM OG

Press

M3

key. (Output Group = OG)

LOW PRODUCT LIMIT OUTPUT GROUP N Press

UP/DOWN

to assign alarm to (OG) N

NONE

Not assigned to an OG

GROUP A-FF

One OG selected (A=1st OG, FF=32nd OG)

ALL GROUPS

All OGs selected (see WORKSHEET #6-1)

Press

ENTER

to accept this data.

NOTE