Cpm menu (continued ... from previous page) – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 110

Advertising
background image

19

Page

19 - 2

Tank Sentinel Setup Programming Guide

CPM Menu (Continued ... FROM PREVIOUS PAGE)

CATHODIC PROTECTION

DATA

Press

M1

key.

CATHODIC PROTECTION DATA

ENABLE

Press

M1

key.

CPM ENABLE

Use

UP/DOWN

keys to show choices.

NO

(select

YES if a TS-CPM unit is installed)

YES

Press

ENTER

to accept this data.

ADDRESS

Press

M2

key.

CPM SENSOR ADDRESS

(accessing this menu is not required for SETUP)

112

Keep the default value (112)

CONFIG

Press

M3

key.

CPM SENSOR SETUP

(accessing this menu is not required for SETUP)

CHECKING ADDRESS ...

(the system is searching for the current address)

— Press the

CANCEL key to display the CATHODIC PROTECTION Menu —

ALARM

Press

M2

key.

CATHODIC PROTECTION ALARM

AMPS

Press

M1

key.

CPM CURRENT LIMIT

+10.0000

0.0 to 10 amps

Use keypad to input a current limit number.
Press

ENTER

to accept this data.

AMPS OG

Press

M2

key.

CPM CURRENT LIMIT OUTPUT GROUP

(32 OGs available ... see Worksheet #19-1)

NONE

Not assigned to an Output Group (OG)

GROUP A-FF

One OG selected (A=1st OG, FF=32nd OG)

ALL GROUPS

All OGs selected
Use

UP/DOWN

keys to choose an OG.

Press

ENTER

to accept this data.

— Press the

CANCEL key two times to display the SETUP Menu —

(input 80% of the output amperage
level that was documented on the
last UST Survey Report)