Cvs lines menu 22 – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 133

Advertising
background image

Compliance Via Sensors Setup

Page

22 - 3

22

CVS Lines Menu

After programming the maximum number of sensors from the SYSTEM menu, access
the CVS Lines menu and program each sensor to associate it with a particular line.

The default programming is 0 (no sensor is associated with a Line)

The

TS-LLD

(line leak detector) is not disabled by CVS for lines

Up to 4 different sensors (Sensor A – D) can be associated with a single line

Sensors can only be associated to one line

The maximum sensor number is determined by No. Sens[ors]

(number of sensors)

under the SYSTEM menu

A sensor that is associated to a CVS line must be physically present (wired to the
Tank Sentinel Console – at sensor channel number N).

See the console I.S.

Sensor PC Board to verify which channels are used/wired-to

A sensor cannot be associated to both a Tank and Line

A SENSOR UNAVAILABLE

error message

is displayed if any of the above error

conditions

(italic)

are present

Press the MENU key and press:
SETUP

Press the

M1

key under the word SETUP

Press the

M

key under the word CVS

Press the

M2

key under the word LINES at the Compliance Via Sensors menu

CVS LINES

(MORE)

LINE 1

LINE 2

LINE 3

LINE 4

First display menu

LINE 5

LINE 6

LINE 7

LINE 8

Second display menu

Press the

Menu Select key

under the LINE N, or press the

DOWN

Key if (MORE) is shown in the second display menu for

LINES 5 to 8 (only on consoles that accept more than 4 lines)

COMPLIANCE SENSOR CVS LINE N

(N = Line number)

SENSOR A

SENSOR B ....

COMPLIANCE SENSOR A

Press the

M1

key.

COMPLIANCE SENSOR A CVS LINE 1

0

1 - 32

Use keypad to input

the sensor number that is

associated with this particular line.
Press

ENTER

to accept this data.

— Repeat for each SENSOR letter and for each Line number —

— Press the CANCEL key to return to the previous menu —

Advertising