Problem Solving

Page

29 - 5

29

NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

#

Printed / Faxed / Displayed
Alarm / Warning Text:

Alarm Type:

System WARNING / Error Descriptions and
ALARM Descriptions

(actions to take)

LEAK (Continued… )

SYSTEM

3. Second confirming failure: Call Service
provider / local Regulatory Agency / Manager per
policy procedure at your site or 4. Second Test
passes [false leak failure]... turn pump and
dispenser power back on and restore normal
operation.

48

LEVEL ERROR / LEVEL ERR
/ LVL ERR

SYSTEM

WARNING - product Level - calculation Error

(call

service provider to fix this problem)

49

MEMORY ERROR / MEM
ERR

SYSTEM

WARNING - Memory Error (power quality problem,
or memory-backup battery is dead...

have service

provider check / replace battery and verify that
unit works correctly as originally programmed)

50

NO PROBE / NO PROB

SYSTEM

Diagnostic WARNING - No Probe Detected NO
PROB

(call service provider to correct this

problem)

51

PAPER OUT

SYSTEM

The printer is out of paper

(add new roll of TS-TP2

thermal paper)

52

POWER DOWN

SYSTEM

WARNING - Power Down (time that the unit lost
power or was turned off
)

53

POWER UP

SYSTEM

WARNING - Power Up (time that the unit was
powered up / regained power)

54

PROBE SYNC / PRB SYC

SYSTEM

Diagnostic WARNING - signal lost from Probe
(PRB SYC

call service provider if continuous)

55

RTC FAILURE

SYSTEM

Real Time Clock has failed. Clock and Calendar
settings are affected. Verify date and time are
correct (use CHECK key). Change settings as
needed. Cycle power. Verify settings (use CHECK
key).

56

RTD TABLE ERROR / RTD
TBL ER / RTD TBL

SYSTEM

WARNING - Number of RTDs Error does not
match actual / setup - programmed value

(call

service provider to correct this problem)

57

SCALD TEST FAILED /
SCALD DETECTED LEAK

SYSTEM

WARNING - SCALD Leak Test Failed alarm report
for Tank N

(run a Standard leak test for that

tank... See LEAK)

58

SEN DAT / SENS DATA /
SENSOR DATA ERROR

SYSTEM

WARNING - a BriteSensor @ Channel #N is
sending data errors

(call service provider ASAP)

59

SENS LOSS OF SIGNAL /
SIG LOST / SEN SIG

SYSTEM

WARNING - no data sent / signal lost from
BriteSensor @ Channel #N

(call service provider

ASAP to correct this)

60

SENSOR ID ERROR /
SENSOR ID / SENS ID

SYSTEM

WARNING - a Standard sensor or BriteSensor
was incorrectly typed / identified

(call your service

provider to correct this)