Problem Solving

Page

29 - 3

29

NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

#

Printed / Faxed / Displayed
Alarm / Warning Text:

Alarm Type:

System WARNING / Error Descriptions and
ALARM Descriptions

(actions to take)

25

DRY WELL

SENSOR

TSP-MWS ground water Monitoring Well
BriteSensor is not submerged in water @ Channel
#N

(it cannot detect a product leak unless it's

submerged in ground water... the well may not be
deep enough or the sensor long enough... contact
service provider)

26

EXTERNAL INPUT

SENSOR

External N input module has detected an input
signal

(follow policy procedure at your site).

27

HIGH BRINE

SENSOR

TSP-HIS BriteSensor @ Channel #N detected a
High Brine level

(Call service provider [to confirm

leak] and call your local Regulatory agency. Shut
down pump & dispenser if a leak test has failed on
that tank and see procedures at your site.)

28

LIQUID DETECTED / LIQUID

SENSOR

Standard Sensor @ Channel #N detected a liquid
(run a tank leak test [depending on the sensor
location] and call service provider to identify the
liquid and retest sensor)

29

LOW BRINE

SENSOR

TSP-HIS BriteSensor @ Channel #N detected a
Low Brine level

(Call service provider [to confirm

leak] and call your local Regulatory agency. Shut
down pump & dispenser if a leak test has failed on
that tank and see procedures at your site.)

30

PRODUCT PRESENT /
PRODUCT DETECTED

SENSOR

TSP-DIS, -DDS, -DTS, -MWS BriteSensor @
Channel #N detected Product / leak

(Call service

provider [confirm leak] call the local Regulatory
agency. Shut down pump & dispenser for that
tank and see procedures at your site. [replace
sensor])

31

STANDARD ALARM /
STANDARD INPUT

SENSOR

A Standard Sensor (type TSP-EIS, -HLS, -ULS) @
Channel #N has detected liquid

(run a tank leak

test [depending on the sensor location] and call
service provider to identify the liquid and retest
sensor)

32

SUMP FULL

SENSOR

TSP-DDS, -DTS BriteSensor @ Channel #N
liquid... Sump Full alarm

(see site policy about

pumping containment sump waste water)

33

VAPOR DETECTED / VAPOR

SENSOR

TSP-DVS BriteSensor @ Channel #N detected
product Vapor in the vapor monitoring well

(Call

service provider [to analyze the leak], call your
local Regulatory agency, and see procedures at
your site.)

34

WATER DETECTED

SENSOR

TSP-DIS*, -DDS, DTS, DVS* BriteSensor @
Channel #N detected Water, some sensors* may
not be able to detect product when water is
present

(see procedures at your site)