Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 171

Advertising
background image

29

Page

29 - 6

Tank Sentinel Setup Programming Guide

NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

#

Printed / Faxed / Displayed
Alarm / Warning Text:

Alarm Type:

System WARNING / Error Descriptions and
ALARM Descriptions

(actions to take)

61

SENSOR SYNC ERROR /
SENSOR SYNC / SEN SYN

SYSTEM

WARNING - data signals not synchronous from
BriteSensor @ Channel #N

(call service provider

ASAP to correct this)

62

CORRECTION (STRAPPING)
TABLE ERROR / TABLE ERR
/ TBL ERR

SYSTEM

WARNING - Tank Strapping Chart or Table...
setup Error (call service provider to correct)

63

TEMPERATURE ERROR /
TEMP ERROR / TMP ERR

SYSTEM

WARNING - probe/product Temperature -
calculation Error (TMP ERR

call service provider

to correct this problem)

64

THEFT DETECTED / THEFT
LIMIT

SYSTEM

WARNING - Sentinel Mode: Theft Detected (the
amount of product missing reached the Theft Limit)
alarm report for Tank N

65

TS-SEM FUSE OPEN / SEM
FUS / SEM FUSE

SYSTEM

WARNING - TS-SEM FUSE OPEN @ BriteBox #1
or #2... [#1 is closest to the console] there is no 5
VDC …Leak Detection Sensors wired to the
BriteBox won't function !

(call service provider to

troubleshoot/replace TS-SEM FUSE F1)

66

UNSTABLE PROBE / UNST
PROBE / UNST PB / UNST
PB

SYSTEM

WARNING - the signal from Probe N has become
Unstable

(call service provider to correct)

67

VOLUME ERROR / VOLUME
ERR / VOL ERR (also see
level, net, ullage, water error)

SYSTEM

WARNING - product - Volume calculation error
(Error in programming: tank shape / probe type /
special probe - OR - no level signal from probe.
Call service provider to correct this.)

68

WATCHDOG TIMEOUT / WD
TIMEOUT

SYSTEM

WARNING - the console self-monitoring program
has detected a software or power quality problem
(this error may happen after hardware upgrades)

69

WATER VOLUME ERROR /
WTR VOL ER / WTR VOL

SYSTEM

WARNING - Water Volume calculation error
(Error in tank shape / probe type or special probe
data - OR - no water float / level signal from probe.
Call service provider to correct this.)

70

HIGH HIGH / HIGH HIGH
LIMIT

TANK

High High product level Limit @ Tank N

(see

procedures at your site about this alarm / overfill)

71

HIGH LIMIT

TANK

High product level Limit @ Tank N

(see

procedures at your site about this alarm / overfill)

72

LARGE THEFT

TANK

Generated by TS-DIM unit. The amount of product
dispensed exceeded the programmed User
Threashold value, and/or exceeded the number of
Dispensers in use. Also caused by a Catastrophic
Leak. (see policy procedures at your site)

73

LOW LIMIT

TANK

Low product level Limit @ Tank N

(see policy

procedures at your site)

Advertising