Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 169

Advertising
background image

29

Page

29 - 4

Tank Sentinel Setup Programming Guide

NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

#

Printed / Faxed / Displayed
Alarm / Warning Text:

Alarm Type:

System WARNING / Error Descriptions and
ALARM Descriptions

(actions to take)

35

ALPHA ERROR / ALPHA ERR
/ ALPHA V

SYSTEM

Error in API temperature compensation calculating
ALPHA (check any Special Products -- reprogram
temperature compensation type & API ALPHA
value).

36

API ERROR / API VOL

SYSTEM

Error in API temperature compensation routine
(check any Special Products -- reprogram
temperature compensation type).

37

CPM FAILURE

SYSTEM

No Power / Power is below 5 VDC - Check Power
Supply / Increase Voltage (if possible)

38

CPU CRASH

SYSTEM

WARNING - Central Processing Unit / hardware
failure / power quality problem

39

DATA ERROR / DIM

SYSTEM

Transient communication error between the Tank
Sentinel and TS-DIM unit. This alarm/error will
clear itself automatically.

40

DATA NOT AVAILABLE / DIM

SYSTEM

Transient alarm/error caused when TS-DIM unit is
'busy' performing another task and cannot make
the requested data available until it is not 'busy'.
This alarm/error will clear itself automatically.

41

DIM COMM FAILURE

SYSTEM

Tank Sentinel has lost communications with the
TS-DIM unit. Verify power to the DIM / Verify
proper connection between DIM and console.

42

F14 OPEN / F14 FUS

SYSTEM

WARNING - FUSE F14 is blown... no 5 VDC
Sensor Supply Power. Leak detection sensors are
not working and cannot work without power

(call

service provider immediately to replace F14)

43

FAX HARDWARE FAILURE /
FAX HW FAIL / FAX FAL

SYSTEM

WARNING - Fax Hardware Failure... alarms &
compliance faxes cannot be sent

(call service

provider ASAP)

44

FAX SND FAIL / FAX SND

SYSTEM

WARNING - Fax Send Failure...

(check Dial tone,

cable, call service provider... are the fax phone
numbers correct ?)

45

FLOAT HEIGHT / FLOAT HT /
FLT HT

SYSTEM

WARNING - Float Height - calculation Error

(setup

program error... call service provider)

46

FLOAT MISSING / FLT
MISSNG / FLT MIS

SYSTEM

WARNING - diagnostic warning Float Missing

(call

service provider)

47

LEAK

SYSTEM

WARNING - a Leak detected @ Tank N during the
after hours Sentinel mode

(shut down dispensing,

see procedures at your site... 1. Shut off pump /
dispenser power 2. Retest / start a Standard 0.2
gph tank test for Tank N, 2 hours after the last
dispense 3. Retest & See Chapters 3 & 4

Advertising