Tanks – tank data n menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 27

Advertising
background image

2

Page

2 - 4

Tank Sentinel Setup Programming Guide

Tanks – TANK DATA N Menu

(C

ONTINUED

...

FROM

PREVIOUS

PAGE

)

TANK ALARM N

To select Tank N ...

COPY

(COPY is optional) Press the

M1

key.

COPY FROM TANK ALARMS X TO N

TANK 1

Select a tank to copy data from (use

M

key).

:

Use

UP

/

DOWN

▲▼

keys to display tanks 5-8.

TANK 8

(The alarm copy function copies all alarm limits

COPY TANK ALARMS X TO N

from Tank X to the current Tank # N)

PRESS ENTER IF YOU ARE SURE?

Press

ENTER

to accept this data.

HIGH LIM
HIGH PRODUCT LEVEL LIMIT N

+96.0000

0.0 to 9999.0

Use keypad to input limit in inches or centimeters.
Press

ENTER

to accept this data.

H LIM OG

(assign Alarm Limits to Output Group)

HIGH PRODUCT OUTPUT GROUP N

(32 OGs available... see Worksheet #2 or #3)

NONE

Not assigned to an output Group (OG)

GROUP A-FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

HIGH HIGH N

N refers to / represents a tank number

HI HI PRODUCT LEVEL LIMIT N

+96.0000

0.0 to 9999. (enter alarm limit)

Press

ENTER

to accept this data.

HH LIM OG N

(assign Alarm Limits to Output Group)

HI HI PRODUCT OUTPUT GROUP N

(32 OGs available... see Worksheet #2 or #3)

NONE

Not assigned to an output Group (OG)

GROUP A-FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

LOW LIM N

N refers to / represents a tank number

LOW PRODUCT VOLUME LIMIT N

+0.0000

0.0 to 50000 (enter alarm limit)

Press

ENTER

to accept this data.

L LIM OG N

(assign Alarm Limits to Output Group)

LOW PRODUCT OUTPUT GROUP N

(32 OGs available... see Worksheet #2 or #3)

NONE (A to FF, or ALL)

Not assigned to an output Group (OG)

GROUP A-FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

LOW LOW N
LOW LOW PRODUCT VOLUME LIMIT N

+0.0000

+ 0 to 50000 (enter alarm limit)

Press

ENTER

to accept this data.