Calibrt menu 28, Calibrt 28, Calibration procedure 28 – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 164

Advertising
background image

Diagnostic Menu

Page

28 - 5

28

CALIBRT Menu

CALIBRT

Here is the SELECT DIAGNOSTIC OPTION menu
displaying RESET, DIPSW and CALIBRT menu
names.

Press the

M3

key under CALIBRT.

The CALIBRATE PUMP 1 display asks if the user
is sure before enabling automatic calibration for a
particular pump controller; giving the user a chance
to press

CANCEL

to abort the calibration process.

Press the

ENTER

key to enable calibration for the

pump controller.

(Press the

CANCEL

key to abort the process.)

After enabling calibration, the display will flash the word DONE ... for a
few seconds and then it will automatically return to the SELECT
DIAGNOSTIC OPTION menu, displaying RESET, DIPSW and CALIBRT.

Calibration Procedure

When calibration is enabled, all three LEDs on the pump controller are blinking ....

1.) Verify this condition.

2.) Turn on the hook signal for greater than 16 seconds to trigger automatic calibration.

After 16 seconds, the controller will take a snap shot of the voltage, current and power (i.e.

these are the Calibrated status values) seen in the Display feature mentioned earlier.

Once complete, the LEDs stop flashing and the Green light remains flashing.

3.) Verify this condition.

4.) Turn off the hook.

5.) Verify that the Tank Sentinel display has returned to the RUN MODE, showing

SYSTEM, TANK, SENSOR, etc. are all OKAY.

— Proceed to Chapter 29 - Problem Solving

In the following examples, “N”
represents any pump number -
1, 2, 3 and so on.

NOTE

SELECT DIAGNOSTIC OPTION

RESET

DIPSW

C A L I B R T

M1

M2

M3

M4

E N A B L E A U T O C A L O N P U M P 1
A R E Y O U S U R E ?