Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 139

Advertising
background image

TS-TPI Setup Programming

Page

23 - 5

23

PUMP N Menu

continued —

TYPE

“READ ONLY”

Here is the PUMP N menu.

Press the

M2

key to display the TYPE

PUMP N “READ ONLY” field ....

In this example, type ‘VFC’ is displayed ....

There are five types of controllers-
VFC, SC, SCIII, SCI and VFCIV.

— Press the CANCEL key to return to the PUMP N menu —

— Proceed to the next menu - GROUP

GROUP

“READ ONLY”

Here is the PUMP N menu.

Press the

M3

key to display the GROUP

PUMP N “READ ONLY” field ....

In this example, group “2” is displayed ....

The group value may be 1 to 4. This menu
item defines which group or TS-TPI port
number is attached to which pump. A value
of 1, 2, 3 or 4 will indicate that the controller
is on that port. Any Line Leak Detectors will
be on Group 1, therefore the first pump group
is 2.

— Press the CANCEL key to return to the PUMP N menu —

— Proceed to the next menu - ADDRESS

GROUP PUMP 1

READ ONLY

2

TYPE PUMP N

READ ONLY

V F C

PUMP N

(MORE)

NAME

T Y P E

GROUP

ADDRESS

M1

M2

M3

M4

PUMP N

(MORE)

NAME

TYPE

G R O U P

ADDRESS

M1

M2

M3

M4