Tank leak test menu 10, Tank leak test menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual
Page 70

10
Page
10 - 2
Tank Sentinel Setup Programming Guide
Tank Leak Test Menu
N = Tanks 1 – 8
(only the number of tanks programmed in
the System menu will appear)
Setup the confidence percentage
CONFIDENC
Press
M1
key.
LEAK TEST CONFIDENCE
99.0(%)
Use
UP/DOWN
▲
▼
keys to show choices.
90.0%
Press
ENTER
to accept this data.
95.0%
97.5%
Setup the percision of the leak test
PRECISION
Press
M2
key.
LEAK TEST PRECISION
Select tank number using (
M
) key.
TANK 1
TANK 2
:
TANK 8
(NOTE: 5 – 8 TS-2001/508 only)
LEAK TEST PRECISION
+0.20000
0.05 to 2.0
Use keypad to input a precision number.
Press
ENTER
to accept this data.
Setup a minimum amount of time to test for leaks per local regulations —
MIN LK TM
Press
M3
key.
MINIMUM LEAK TEST TIME
2
2 to 8.0 hours
Use keypad to input minimum leak test time.
Press
ENTER
to accept this data.
— Continued next page —
Monthly
Compliance
Yearly Test
Static Leak Test:
0.2 gph
0.1 gph
Precision Tank # 1
Precision Tank # 2
Precision Tank # 3
Precision Tank # 4
Precision Tank # 5
Precision Tank # 6
Precision Tank # 7
Precision Tank # 8
Threshold = 1/2 of Leak Test value