System Setup

Page

1 - 5

1

S

YSTEM

Menu (C

ONTINUED

...

FROM

PREVIOUS

PAGE

)

REP LINES

(Appears only if an L is present in the TS Part

REPORT LINE TESTS

Number (press CHECK and M4 to view OPTIONS)
Use

UP/DOWN

keys to choose.

Press

ENTER

to accept this data.

ENABLED

(enabled = yes, report LINE leak tests)

DISABLED

(disabled = no, don’t report LINE leak tests)

HIST SIZE

(Max. number of alarms in Alarm History Reports)

HISTORY REPORT LENGTH
50

enter range from 1 to 50 alarms shown.

Press

ENTER

to accept this data.

SYSFL OG

(assign system fail warnings to Output Group)

SYSTEM FAIL OUTPUT GROUP

(32 OGs available... see Worksheet #1)

NONE

Not assigned to an Output Group (OG)

GROUP A

thru

FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL

GROUPS

All OGs selected
Use

UP/DOWN

keys to choose an OG.

Press

ENTER

to accept this data.

PRNT INTR

(how many intervals to print)

STRAPPING TABLE PRINT INTERVAL
+1.000

enter strapping table print interval,

range = 1 to 100.0 level units.
Press

ENTER

to accept this data.

DATA INTR

(for diagnostic use)

DATA CAPTURE INTERVAL
1

data logging interval, range = 1 to 9999.

Press

ENTER

to accept this data.

DATA TANK

(for diagnostic use)

TANK TO DATA LOG
1

tank(s) to data log, range = 1 to NO. of TANKS.

Press

ENTER

to accept this data.

COLD BOOT

(Will erase all program data / setup data to the

IF YOU CONTINUE, ALL SYSTEM

original “factory” default values)

PROGRAMMING AND DATA WILL BE LOST...

PRESS ENTER IF YOU ARE SURE THAT

Press

ENTER

to proceed with the ‘COLD BOOT’.

YOU WANT TO CONTINUE WITH COLD BOOT

ERASING SYSTEM MEMORY ...
SYSTEM WILL REBOOT WHEN

(The ATG SETUP programming is returned to the default

COMPLETE

settings and must be reprogrammed to match the site.)