Problem Solving (Alarms & Errors)

Problem Solving

The following table lists alarms and errors in alphabetical order.

Notice they are

grouped by ‘Alarm Type’ in the middel section. Contact INCON for more help.

Contents:
Problem Solving
Outputs DON’T Turn On When

Expected

See the Table of Contents to find topics in
this manual. See the Preface for general
information about this manual. Also see the
Installation, Operator’s, TroubleShooting
Guides, and Application Notes for other
reference sources.

NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

#

Printed / Faxed / Displayed
Alarm / Warning Text:

Alarm Type:

System WARNING / Error Descriptions and
ALARM Descriptions

(actions to take)

1

0.1 GPH LINE LEAK
DETECTED

LINE

For LINE # N: Line Leak Detected / Leak Test
Failed

(1. Inspect dispense area for leaks 2.

Retest if no leaks seen 3. Shut off pump /
dispenser power

2

0.1 GPH ABORT (DISPENSE)

LINE

Attempted dispense causes the annual line leak
test to aborted (dispensing is not allowed during
this test). To allow dispensing: push the RESET
/ TEST button on the TS-LLD Control Unit that is
flashing the 80 alarm-error-code.

See the TS-LLD

Quick Reference Guide about the 0.1 gph Annual
Test and requirements.

0.1 GPH LINE LEAK
(Continued… )

LINE

4. Second failure: Call Service provider / local
Regulatory Agency / Manager per policy
procedure at your site).

3

0.1 GPH LINE TEST
ABORTED

LINE

The annual precision line leak test was
intentionally canceled / aborted from the Tank
Guage or from the TS-LLD control unit.

4

0.2 GPH LINE LEAK

LINE

Follow the steps detailed above for 0.1 gph Line
Leak Detected

5

3 GPH LINE LEAK

LINE

LINE # N - Line Leak Detected / test failed Large /
gross leak

(see above 0.2 gph line leak & follow

steps 3, 1, and 4 in this order).

6

BLK TUB/LSU BLOCKED
TUBE

LINE

(Push RESET / TEST button on the TS-LLD
control unit that is flashing an 81 Alarm-error code
and call for cleaning service).

7

CU COMM/CU COMM
FAILURE

LINE

Communications was lost between the Tank
Sentinel console and TS-LLD Control Unit …(call
for service).