Probes Setup

Page

4 - 3

4

Probes – PRESSURE PROBE DATA Menu

This

grayed out

section is a duplicate of the STANDARD menu - use it to assist in

following the PRESSURE PROBE DATA MENU.

PROBE DATA N

PROBE # N shown typical for any probe # 1 – # 8.

COPY

Press M1 key.

PROBE DATA N

PROBE # N shown typical for any probe # 1 – # 8.

TYPE

Press M2 key.

PROBE TYPE FOR PROBE N

Press

UP/DOWN

▲ ▼

keys to choose probe type.

PRESSURE

Select PRESSURE (pressure probe).
when programming TS-ISCB or TSP-LLPT probes.

MODEL

Press

M3

key. (instead of GRADIENT for STANDARD)

PROBE MODEL FOR PROBE N

Press

UP/DOWN

keys to choose either (TS-ISCB

or TSP-LLPT)
Press

ENTER

to accept this data.

SCALE (

TS-ISCB

)

Press

M4

key. (instead of NO.FLOATS for STANDARD)

SCALE N
+9.03000

Use the keypad to enter the PSI as printed on the

probe.
Press

ENTER

to accept this data.

OFFSET(

TSP-ISCB

)

Press

M1

key. (instead of FLOAT TYPE for STANDARD)

PROBE OFFSET N
+0

Use the keypad to enter the OFFSET level.

Press

ENTER

to accept this data.

CONFIG (

TSP-LLPT

)

Press

M4

key. (instead of SCALE for ISCB)

CONFIGURING PROBE

(ATG will check the addresses for all probes)

SCALE (

TSP-LLPT

)

Press

M1

key. (instead of OFFSET for ISCB)

SCALE N
+9.03000

Use the keypad to enter the PSI as printed on the

probe.
Press

ENTER

to accept this data.

ENA TEMP (

TSP-LLPT

)

Press

M2

key.

TEMPERATURE ENABLE N
NO

Press

UP/DOWN

keys to choose either (NO or YES)

YES

Press

ENTER

to accept this data.

OFFSET(

TSP-LLPT

)

Press

M3

key.

PROBE OFFSET N
+0

Use the keypad to enter the OFFSET level.

Press

ENTER

to accept this data.

NOTE