Tank Setup

Page

2 - 5

2

Tanks – TANK ALARM N Menu

(C

ONTINUED

...

FROM

PREVIOUS

PAGE

)

LL LIM OG N

(assign Alarm Limits to Output Group)

L L PRODUCT OUTPUT GROUP N

(32 OGs available... see Worksheet #2 or #3)

NONE

Not assigned to an output Group (OG)

GROUP A-FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

WATER LIM N
HIGH WATER LEVEL LIMIT N

+4.0000

0.0 to 9999.0 (enter alarm limit)

Press

ENTER

to accept this data.

W LIM OG N

(assign Alarm Limits to Output Group)

HIGH WATER OUTPUT GROUP N

(32 OGs available... see Worksheet #2 or #3)

NONE

Not assigned to an output Group (OG)

GROUP A-FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

WATER LIM N and W LIM OG N are not available for PRESSURE probes, since they do
not measure water level.

Tanks – SPECIAL TANK N Menu

•

If

STANDARD tanks are selcted, then these menu options will not be available.

•

Correction Tables:

If the Special Tank is not a perfect cylinder or has a domed end,

then you must program a correction table (100 correction points can be programmed).
Two values are required per point / position (POS #). These are level and volume, which
are found in the manufacturers’ tank table /chart, input these accurately. Always input 0
level and 0 volume for the first point, and max. level and max. volume for the last point.
The number of points in between determines the accuracy of the strapping table.

•

Cylindrical Tanks:

Select diameter and input the internal tank diameter value, and

set the length to the internal length of the tank (correction tables are usually not needed
with cylindrical tanks).

•

Vertical or Rectangular tanks: Select diameter and input the internal tank diameter or

depth, and set its

length to zero ( 0 ). Input 0 level and 0 volume for the first point, and

max. level and max. volume for the last point.

•

Correction Points are automatically sorted from lowest to highest level. The lowest

level is closest to the bottom of the tank.

SPECIAL

SPECIAL TANKS

SPECIAL 1
SPECIAL 2

:

Use

UP/DOWN

▲▼

keys to display tanks 5-8.

SPECIAL 8