Tanks - special tank n menu 2, Tanks – tank alarm n menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 28

Advertising
background image

Tank Setup

Page

2 - 5

2

Tanks – TANK ALARM N Menu

(C

ONTINUED

...

FROM

PREVIOUS

PAGE

)

LL LIM OG N

(assign Alarm Limits to Output Group)

L L PRODUCT OUTPUT GROUP N

(32 OGs available... see Worksheet #2 or #3)

NONE

Not assigned to an output Group (OG)

GROUP A-FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

WATER LIM N
HIGH WATER LEVEL LIMIT N

+4.0000

0.0 to 9999.0 (enter alarm limit)

Press

ENTER

to accept this data.

W LIM OG N

(assign Alarm Limits to Output Group)

HIGH WATER OUTPUT GROUP N

(32 OGs available... see Worksheet #2 or #3)

NONE

Not assigned to an output Group (OG)

GROUP A-FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

WATER LIM N and W LIM OG N are not available for PRESSURE probes, since they do
not measure water level.

Tanks – SPECIAL TANK N Menu

If

STANDARD tanks are selcted, then these menu options will not be available.

Correction Tables:

If the Special Tank is not a perfect cylinder or has a domed end,

then you must program a correction table (100 correction points can be programmed).
Two values are required per point / position (POS #). These are level and volume, which
are found in the manufacturers’ tank table /chart, input these accurately. Always input 0
level and 0 volume for the first point, and max. level and max. volume for the last point.
The number of points in between determines the accuracy of the strapping table.

Cylindrical Tanks:

Select diameter and input the internal tank diameter value, and

set the length to the internal length of the tank (correction tables are usually not needed
with cylindrical tanks).

Vertical or Rectangular tanks: Select diameter and input the internal tank diameter or

depth, and set its

length to zero ( 0 ). Input 0 level and 0 volume for the first point, and

max. level and max. volume for the last point.

Correction Points are automatically sorted from lowest to highest level. The lowest

level is closest to the bottom of the tank.

SPECIAL

SPECIAL TANKS

SPECIAL 1
SPECIAL 2

:

Use

UP/DOWN

▲▼

keys to display tanks 5-8.

SPECIAL 8

NOTE