Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 19

Advertising
background image

System Setup

Page

1 - 3

1

S

YSTEM

Menu (C

ONTINUED

...

FROM

PREVIOUS

PAGE

)

NO. SENSORS

(enter the number of Leak Detection Sensors)

NUMBER OF SENSORS
12 (for TS-1001, 504)

(0 thru N) enter the total number of Sensors.

24 (for TS-2001, 508)

(also enter all unused channels between the lowest to
highest channel (also see SENSORS menu)
Press

ENTER

to accept this data.

NO. METERS

(devices used with TS-DIM)

NUMBER OF METERS

0

enter number of meters.

Press

ENTER

to accept this data.

BUSY ENA
BUSY ENABLED

(dispenser supports ‘busy’ signal to ATG)

NO

Use

UP/DOWN

keys to choose setting.

YES

Press

ENTER

to accept this data.

U THRESH

(volume allowed pumped before Catastrophic Leak alarm)

USER THRESHOLD

+0

1 to +9999 volume units.

Press

ENTER

to accept this data.

LIMITS
LIMITS

(set leak limits for after hours sentinel mode – also see

LEAK LIM

menu)

LEAK LIMIT
+2.0

0.2 to +10.0 volume units.

Use keypad to input sentinel mode leak rate.
Press

ENTER

to accept this data.

LEAK OG

(assign leak alarm to an OG (

NONE, A to FF, or ALL)

LEAK LIMIT OUTPUT GROUP

(32 OGs available... see Worksheet #1-1 )

NONE

Not assigned to an Output Group (OG)

GROUP A

thru

FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

THEFT LIM

(enter theft limit for all tanks)

THEFT LIMIT
+10.0

1 to +9999 volume units.

Press

ENTER

to accept this data.

THEFT OG

(assign theft limit alarm to an OG (

NONE, A to FF, or ALL

THEFT LIMIT OUTPUT GROUP

Output Groups)(32 OGs available... see Worksheet #1-1 )

NONE

Not assigned to an Output Group (OG)

GROUP A

thru

FF

One OG selected (

A = 1

ST

OG, FF = 32

ND OG

)

ALL

GROUPS

All OGs selected
Use

UP/DOWN

▲ ▼

keys to choose an OG.

Press

ENTER

to accept this data.

Advertising