Sensors menu (c – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 97

Advertising
background image

17

Page

17 - 2

Tank Sentinel Setup Programming Guide

Sensors Menu (C

ONTINUED

...

FROM

PREVIOUS

PAGE

)

SENSORS

Press (

M

) key.

AUTO CFG

(Automatically identify the sensors) Press

M1

key.

SENSOR 1

Press (

M

) key.

SENSOR 2

Use

UP/DOWN

keys to show more choices.

:

(SENSORS 13 – 28 are

optional with the TS-1001/504)

SENSOR 40

(SENS0RS 25 – 40 are

optional with the TS-2001/508)

NAME

Press

M1

key.

SENSOR NAME N

N = SENSOR channel Number

SENSOR N

9 characters

Use keypad to input / change sensor name (

optional )

Press

ENTER

to accept this data.

TYPE

Press

M2

key.

STD

Use

UP/DOWN

keys to show more choices.

(or TSP

-DIS, TSP-DDS, TSP-DTS,

Press

ENTER

to accept this sensor ... do not change

TSP-HIS, TSP-MWS, TSP-DVS)

any sensor type - use AUTO CFG instead)

Depending on which sensors are installed will determine which of the following alarm Output
Groups (OG) choices will appear. OGs can be assigned to activate annunciators, or control
relays / devices on alarm. OGs are sensor and channel dependant. Document the Sensor
and Output Group Assignments on the Worksheets provided on the following pages.

STD OG

(only for standard sensors)

STANDARD OUTPUT GROUP N
NONE (A to FF or ALL) assign alarm to Output Group N

PROD OG

(with TSP –DIS, DDS, DTS or MWS sensors)

PRODUCT OUTPUT GROUP N
NONE (A to FF or ALL) assign alarm to Output Group N

WATER OG

(with TSP–DIS, DDS, DVS or DTS sensors)

WATER OUTPUT GROUP N
NONE (A to FF or ALL) assign alarm to Output Group N

SMP FL OG

(with TSP–DDS or DTS sensors)

SUMP FULL OUTPUT GROUP N
NONE (A to FF or ALL) assign alarm to Output Group N

DRY WL OG

(with TSP–MWS sensor)

DRY WELL OUTPUT GROUP N
NONE (A to FF or ALL) assign alarm to Output Group N

HGH BR OG

(with TSP-HIS sensor)

HIGH BRINE OUTPUT GROUP N
NONE (A to FF or ALL) assign alarm to Output Group N

LOW BR OG

(with TSP-HIS sensor)

LOW BRINE OUTPUT GROUP N
NONE (A to FF or ALL) assign alarm to Output Group N

VAPOR OG

(TSP-DVS sensors only...

other DVS sensor menus items on next page

)

VAPOR OUTPUT GROUP N
NONE (A to FF or ALL) assign alarm to Output Group N

NOTE

Typical Output Group

Choices

UP/DN

to show choices

ENTER

to select

NONE
A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

R

T

U

V

W X

Y

Z

AA BB CC DD EE FF
ALL