Outputs don't turn on when expected 27 – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 172

Advertising
background image

Problem Solving

Page

29 - 7

29

See the Operators Guide for other error messages that are listed by type.

Outputs DON’T Turn On When Expected

Printout setup report(s)

Check Worksheets for alarm-limit or alarm Output Group assignments

Check output device (Annunciators / Relays / Output modules) for alarm group
assignments.

Correct programming assignments as necessary and retest operation

NOTE

NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

#

Printed / Faxed / Displayed
Alarm / Warning Text:

Alarm Type:

System WARNING / Error Descriptions and
ALARM Descriptions

(actions to take)

74

LOW LOW LIMIT / LOW LOW

TANK

Low Low product level Limit @ Tank N

(see policy

procedures at your site)

75

OVERFILL

TANK

The overfill limit has been reached or exceeded.
Stop filling tank / Lower the product level.(see
policy procedures at your site)

76

WATER LIMIT (or HIGH
WATER)

TANK

The high Water level Limit has been reached or
exceeded @ Tank N

(see procedures at your site

about this alarm, is a Grace Period allowed ? how
many ?)