Logger

• Tmer (<tmerNo>)

Up to eight timers can be specified. The timer is specified using a number between 1

and 8.

Select the timer operation from the choices below. Select Off to disable the timer.

Edge operation: Returns 1.0 when performing computation after the ON time elapses

after the beginning of each interval. Specify the interval for detecting

the condition and the ON time in ms.

Level:

Returns 1.0 from the time after the ON time elapses until after the

OFF time elapses. Specify the interval for detecting the condition,

ON time, and OFF time.

The condition detection interval that can be set is from 1000 ms to 232–1 ms. The
ON/OFF time is specified from the beginning of the interval to the elapsed time.

Tmer Level Operaton

• When ON < OFF

• When ON > OFF

ON setting

OFF setting

t

Interval

Returns 1.0

Returns 1.0

Interval

ON

OFF

ON

OFF

ON setting

OFF setting

t

Interval

Returns 1.0

Returns 1.0

Returns 1.0

Interval

OFF

ON

OFF

ON

Manual AO Functon

Below are the pattern outputs that are available with the manual AO function. The

functions are not case sensitive. Specify <manual> as described in the explanation for

manual and user output in this section. The operation does not take place if the relevant

user output channel is not set to pattern output mode.

Functon

Descrpton

Example

StartPTN()

Start pattern output
Description

ch(00010) >=0 ? StartPTN() : 0

StopPTN()

Stop pattern output
Description

ch(00010) >=0 ? StopPTN() : 0

SuspendPTN()

Pause pattern output
Description

ch(00010) >=0 ? SuspendPTN() : 0

ResumePTN()

Resume pattern output
Description

ch(00010) >=0 ? ResumePTN() : 0

StartPTN(<manual>)

Start pattern output on the
specified user output channel

ch(00001) ==0 ? StartPTN(1) : 0

StopPTN(<manual>)

Stop pattern output on the
specified user output channel

ch(00001) ==0 ? StopPTN(1) : 0

SuspendPTM(<manual>)

Pause pattern output on the
specified user output channel

ManualDO(1)==1 ? SuspendPTN(1)
: Resume(1)

ResumePTN(<manual>)

Resume pattern output on the
specified user output channel

ManualDO(1)==1 ? SuspendPTN(1)
: Resume(1)