Yokogawa DAQWORX User Manual

Page 72

Advertising
background image

2-42

IM WX103-01E

• Error Output [Error]

Outputs a relay contact signal when any of the following events occur in the main

module CPU of a unit containing a digital output module. When the CPU is normal,

the relay is energized and FAIL output is ON. When the CPU is abnormal or if a power

failure occurs, it is OFF.

• A data output request timeout (60 s) occurs while recording data.

(except when the MX100 /DS option functions are enabled)

• A module error occurs.

• An input module detected at power-on that is able to make measurements is

removed.

• A module breaks down.
• An unidentifiable module is attached.

When using the energize setting for contact output, the circuit switches from open

to short when the output is enabled. When using the de-energize setting, the circuit

switches from short to open.

Energzed/De-energzed Operaton of Output Relays

You can select whether the output relay is energized or de-energized when an output

event (such as an alarm) occurs. If de-energized is selected, the output relay behaves in

the same fashion as when an output event occurs if the power is shut down. The default

setting is Energized.

NO

Energize

De-energize

C

NO

C

NO

C

NO

C

NO

C

NO

C

When power is

shut down

NO: Normally Opened, C: Common

When alarm is

not occurring

When alarm is

occurring

Hold/Non-Hold of Output Relays

Select the behavior of the output relay when an output event is released (recovers to a

normal condition). The default setting is Non-hold.

• Turn OFF the output relay with the release of the output event (non-hold).

• Hold the output relay at ON until the Relay ACK button (see below) is clicked.

Relay ACK button

Output cause

occurrence

• When set to non-hold

• When set to hold

Relay output ON

Relay output OFF

Relay ACK

Relay output ON

Relay output OFF

Output cause

occurrence