Logger

The table below shows the relationship between the number of MXLOGGER alarm

settings (by version) and the MX100 hardware style number.

MXLOGGER

MX100 Hardware

Style Number

*2

Notes

Software verson

*1

Connectable module types
or settng tems

S3

S2

S1

R2.05 or later

Alarm level setting (alarm1
to alarm 4)

Yes

No

No

No: Operation possible with alarm 1 and
alarm 2

Yes: Setting and operation allowed

No: Setting possible, but not operation

*1 To check the version, see section 2.16, “Displaying the Software Version and Other

Information.”

*2 The style number is printed on the MX100 main module name plate.

When acquisition is started, the hardware style numbers, alarm settings, and operating

statuses of the connected MX100s are displayed in the Unit Status area in the Run

screen on the Main window.

This indicates that for hardware style S2 or earlier,

even if Alarm 3 and Alarm 4 have been set, they are

not functioning.

Setting and operation with alarm1 to alarm 4 allowed

MX100 Hardware style number

Alarm Hysteress

You can set a width (hysteresis) to the values used to activate and release alarms.

Alarm hysteresis prevents frequent activation and release of alarms when the measured/

computed value is unstable around the alarm value.

Alarm value

Alarm reset

Measured value or

computed value

Alarm occurrence

Upper limit alarm

Lower limit alarm

Measured value or

computed value

Alarm reset

Hysteresis

Alarm value

Alarm occurrence