Yokogawa DR240 User Manual

Page 230

Advertising
background image

12-10

IM DR232-01E

Examples of Setting Using the Event/Action Functions

• Sum the values measured on channel 001 from 8:00 to 9:00 every day.
Setting the MATCH TIME field:
Configure the DR recorder so events occur at 8:00 and 9:00 every day.

MATCH TIME No.=1

1 2 3

1:TIME=00 08:00

>Set Day & Time DD HH:MM:00

***SET OK***

(configuration complete)

MATCH TIME No.=2

1 2 3

1:TIME=00 09:00

>Set Day & Time DD HH:MM:00

***SET OK***

(configuration complete)

MATCH TIME

ENTER

ENTER

ENTER

SET=

(Main menu item)

(Submenu items)

ENTER

ENTER

ENTER

ENTER

Selects match timer no. 1.

Sets the date to 00 and time to
8:00.

Selects match timer no. 2.

Sets the date to 00 and time to
9:00.

Setting the EVENT/ACTION fields:
Configure the DR recorder so it uses the match time as the event to clear computed values and
then start computing at 8:00 and ends computing at 9:00.

LOGIC BOX No.=1

(01 to 30)

EVT=MATCH TIME:1

ACT=EDGE / MATH : CLEAR

***SET OK***

(configuration complete)

LOGIC BOX No.=2

(01 to 30)

EVT=MATCH TIME:1

ACT=EDGE / MATH : START

***SET OK***

(configuration complete)

LOGIC BOX No.=3

(01 to 30)

EVT=MATCH TIME:2

ACT=EDGE / MATH : STOP

***SET OK***

(configuration complete)

LOGIC

ENTER

ENTER

ENTER

SET=

(Main menu item)

(Submenu items)

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

Selects match time 1.

Selects match time 1.

Selects match time 2.

Provides the setting
for clearing computed
values.

Provides the setting
for starting computing.

Provides the setting
for ending computing.

Computation equation:
CALC=TLOG.SUM (001)

If, in the event/action functions, you have assigned the same event to more than one LOGIC BOX
number at the same time, the DR recorder executes computing, beginning with the smallest
LOGIC BOX number. In the above configuration, the DR recorder clears computed values at
8:00 and starts computing. The values and behaviors of the event/action functions when
computing is done with the above configuration are as follows: