4-3

IM DR232-01E

4

Setting the Monitor Mode Display

AUTO Display for Sub-display 1

Data of two channels are displayed here simultaneously.

Channel No., Difference between Channels (delta), Alarms, Measurement Values

Same as for the main display.

Engineering Units

If the channel number has been selected to appear on the display, the first four characters of the
unit setting are used for displaying engineering units. If TAG has been selected to appear on the
display or when “ XXXXXX” or “ OOOOOO” are displayed as measurement value, no
engineering unit will be displayed.

Selected Display Mode (refer to page 4-1 for procedure)

This only appears on sub-display 1 when monitoring. The arrow shows to which display the
display mode refers.

004d L 0.0926V

005

0.0824V

AUT

Selected display mode

Engineering unit

Measurement value

Alarm

Difference between channels

Channel No.
1st digit: unit No. A will be displayed in the case of optional

computation channels.

2nd digit: slot No.
3rd digit: channel No. (in units of 1)

Others

Same as for the main unit.

AUTO Display for Sub-display 2

Data of two channels are displayed here simultaneously.

Channel No., Difference between Channels (delta), Alarms, Measurement Values,
Engineering Units and Selected Display Mode

Same as for the sub-display 1.

Others

Same as for the sub-display 1.

Points to Note when Using the AUTO Display

• When all three displays are set to AUTO display, the main display will start displaying data of

the channel with the smallest channel number, on sub-display 1 data of the next two channels
will be displayed, while on sub-display 2 data of the next two channels will be displayed. When
the data are updated, the display will be replaced with data of the next, consecutive, channel.

• When the input type of all channels is set to “SKIP”, then depending on the display as

described below, “***ALL SKIP***” will be displayed.

• When the main display is set to AUTO display, then this will be displayed settings on the

main display, regardless of the settings of sub-display 1 and 2.

• When sub-display 1 is set to AUTO display, and the main display is set to any other mode

than AUTO, then this will be displayed on sub-display 1, regardless the setting of sub-
display 2.

• When sub-display 2 is set to AUTO display, and the main display is set to any other mode

than AUTO, and sub-display 1 to any other mode than AUTO, then this will be displayed on
sub-display 2.

• When on any of the main, sub-display1 or sub-display 2 “***ALL SKIP***” appears, other

displays which may have been set to AUTO will turn blank. Only the selected display mode
on sub-display 1 and the status display will appear.