9 di/do module, Di/do module -27 – Yokogawa DR240 User Manual

Page 272

Advertising
background image

14-27

IM DR232-01E

Specifications

14

14.9 DI/DO Module

Style Number: S2

General Specifications

Terminal type

screw

Normal operating temperature/humidity

20 to 80%RH for 0 to 40

°C, 10 to 50%RH for 40 to 50°C (no condensation)

Power consumption

Included in the main unit or the subunit to which the module is to be installed.

Dielectric strength

Between input terminal and ground: 1500V AC (50/60Hz) for one minute.
Between output terminal and ground: 2300V AC (50/60Hz) for one minute.

External dimensions

Approx. 57 (W)

× 137 (H) × 68 (D) mm

Weight

0.35kg

DO: Alarm output

Output update rate

every measurement interval

Contact mode

Transfer contact (NO-C-NC)

Energize/de-energize

switchable

hold/non-hold

switchable

Reflash alarm

can be set

Contact rating

250V DC/0.1A (resistive load)
250V AC/2A (resistive load)
30V DC/2A (resistive load)

DO: Failure output

Function

The output relay for a failure becomes de-energized when an error is detected in the system of the
DA100 main unit or the DA/DR subunit which is connected to the module.

Contact mode

Transfer contact (NO-C-NC)

Energize/de-energize

not switchable

Contact rating

250V DC/0.1A (resistive load)
250V AC/2A (resistive load)
30V DC/2A (resistive load)

DO: Chart-end Output

Function

The output relay for chart-end becomes energized when the recorder runs out of chart paper.

Contact mode

Transfer contact: normal open/common/normal close type

Energize/de-energize

not switchable

Contact rating

250V DC/0.1A (resistive load)
250V AC/2A (resistive load)
30V DC/2A (resistive load)