3.5 Connecting the Interface Cables

For details on connectin the RS-422-A/RS-485 connector of the RS-422-A/RS-485
communication interface module to a personal computer, see IM DR231-11E, “DR231/DR232/
DR241/DR242 Communication Interface User’s Manual.”

CAUTION

When (dis) connecting the RS-422-A/RS-485 cable, turn OFF the power
of both the personal computer and the instrument. If the power is not
turned OFF, malfunctions may occur and the internal circuitry may be
damaged.

Ethernet

Tx (yellow)

)

LINK (yellow)

STS1 (green)

STS2 (green)

Status

Indicator LED

Dip Switch

1 2 3 4

ON

OFF

10BASE-T Port

Connect the RJ-45 modular jack
of the twist pair cable connected
to the 10BASE-T network.

You can select the following three modes by setting the dip switch.
Configuration mode:

A mode in which the IP address, subnet mask, and default gateway are set
for the DR.

Test mode:

A mode in which the condition of the physical connection is tested.

Communication mode: A mode in which the DR is connected to the network to carry out

communication. Use this mode to read in the DR measurement data with
the PC.

In addition, you can turn ON/OFF the Keepalive function.

Mode Setting

Mode

Switch 1

Switch 2

Configuration mode

ON

OFF

Test mode

OFF

ON

Communication mode

OFF

OFF

←Default Setting

Do not set both dip switches, 1 and 2, to ON.

Keepalive Setting

Keepalive

Switch 3

Enable

ON

Disable

OFF

←Default Setting

Keepalive is a function supported by TCP. It sends packets at constant time intervals and
automatically disconnects when there is no corresponding response. This instrument sends
packets at 30-second time intervals. If a response is not received, it sends 4 more packets at one-
second intervals. If a response is still not received, the connection is dropped.

Have dip switch 4 turned OFF.