14.3 Specifications of mA-input Module

Style Number: S5
Model Code, Number of Input Channels, Terminal Configuration and Shortest
Measurement Interval

Model Code

Number of Channels Terminal Configuration

Shortest Measurement Interval

DU300-11

10

Screw

0.5 s

DU300-12

10

Clamp

0.5 s

Method of Input

Non-balanced floating input with isolation between channels (separated channels)

Resolution of A/D Conversion

±20000

Integral Time of A/D Conversion

Manual or automatic selection between 20 ms (50 Hz), 16.7 ms (60 Hz) and 100 ms (10 Hz)
(Except, auto switch does not function on the subunit (DS400/DS600) of a DC power supply
model. Selecting "AUTO" will set the A/D integration time to 20 ms (50 Hz).)

Shortest Measurement Interval and Cutoff Frequency

When the lowpass filter is turned off:

Cutoff frequency:

50/60 Hz

10 Hz

Shortest measurement interval:

0.5 s

4 s

When the lowpass filter is turned on:

Cutoff frequency:

50/60 Hz

10 Hz

Shortest measurement interval:

3 s

12 s

Normal Operating Temperature/Humidity Range

-10˚ to 60˚C
20 to 80% RH for an ambient temperature range of -10˚ to 50˚C; 10 to 50% RH for 40˚ to 50˚C; 5
to 30% RH for 50˚ to 60˚C (non-condensing)

Maximum Input Voltage

5 V DC

Maximum Normal-mode Noise Current

24 mA (peak value, including 50- and 60-Hz signal components)
Equivalent voltage of 2.4 V

Normal Mode Rejection Ratio (Equivalent Voltage)

40 dB minimum (50/60 Hz

±0.1%)

Maximum Common Mode Noise Voltage

250 V ACrms (50/60 Hz)

Common Mode Rejection Ratio (Equivalent Voltage)

120 dB minimum (50/60 Hz

±0.1%)

Maximum Noise Across Channels

150 V ACrms (50/60 Hz)

Measuring Range/Accuracy

As described below, under the following operating conditions:
Ambient temperature: 23

±2°C; ambient humidity: 55 ±10% RH; power supply voltage: 90 to 250

VAC (AC power supply)/10 to 32 VDC (the subunit of a DC power supply model only); power
supply frequency: 50/60Hz within

±1% (AC power supply); warm-up time 30 minutes or more;

vibrations and others not affecting instrument operation.

Measuring Range

Measuring Accuracy Maximum Resolution

-20.000 to 20.000 mA

±(0.25% of rdg. + 5 digits)

1

µA