IM DR232-01E

DI: Remote control of recorder functions

Function

The following functions can be controlled by contact input:
- alarm acknowledge;
- alarm reset;
- timer reset;
- starting/stopping recording;
- manual printout;
- digital printout;
- message printout;
- message display;
- changing chart speed/recording interval;
- group trend recording;
- Starting/stopping/clearing/resetting computation;
- Saving/reading measured/computed data, reading set-up data.

Input signal

No voltage contact, open-collector driven by a TTL or transistor
Rated voltage:0 to 5 V DC (input impedance:4.7k

Ω, 5 V DC pull up)

Maximum input voltage (allowable range)

–2 to 7 V DC

Input conditions

• ON voltage:0.5V max. (30mA DC)
• Leakage current at OFF state:0.25mA max.

Duration of input signal

one second or longer (input signal detection internal:approx. 0.5 seconds)

14.9 DI/DO Module