7 connecting the signal lines, Connecting the signal lines -20, Wwarning – Yokogawa DR240 User Manual

Page 65: Caution

Advertising
background image

3-20

IM DR232-01E

3.7

Connecting the Signal Lines

W

WARNING

• To prevent electric shock, always make sure that the power supply is

turned OFF before connecting.

• When 30 VAC or 60 VDC and more is applied to the output terminal of

the alarm module or the output terminal of the DI/DO module, use
double-insulated wires(withstand voltage performance: more than 2300
VAC) for those wires which apply 30 VAC or 60 VDC and more. All
other wires can be basic-insulated(withstand voltage performance: more
than 1350 VAC). Furthermore, use “crimp-on” lugs (for 4 mm screws)
with insulation sleeves for connecting to the screw terminal. Make sure
that the crimp-on tool must be one specified by the crimp-on lugs
manufacture, and that the crimp-on lugs and tool must be matched to
the wire size. To prevent electric shock, do not touch the terminal after
wiring and make sure to re-apply the cover.

CAUTION

• Do not apply an input voltage exceeding the following levels to each

terminal of each module. Otherwise, the internal circuits may be
damaged.
Allowable input voltage

Universal or DCV/TC/DI input module

2 VDC range or less, RTD, TC and DI(CONT) :

±

10 VDC

6 to 20 VDC range, DI(LEVEL) :

±

60 VDC

Digital Input module

CONT(Voltage-free contact input) :

±

10 VDC

LEVEL(Voltage input) :

±

60 VDC

mA-input module :

±

5 VDC

Strain input module : Don’t input voltage to the terminal.
Pulse input module : 5 VDC
DI/DO module : –2 to 7 VDC

Max. common mode noise voltage

Universal, DCV/TC/DI input, digital Input, mA-input modules : 250
VACrms (50/60 Hz)

• Output contact rating for DI/DO or Alarm input modules is 250 VDC/0.1

A (resistive load), 250 VAC/2 A (resistive load), 30 VDC/2 A (resistive
load).

• The overvoltage category of each input module is CAT ll (IEC 1010-1).
• When connecting to a clamp terminal, use a signal conductor with the

following cross-sectional width:

Solid conductor

0.14 to 2.5 mm

2

Stranded conductor

0.14 to 1.5 mm

2

AWG

26 to 14

Advertising