3 external voltage supply, External voltage supply – Lenze E84DGFCR User Manual
Page 25
![background image](/manuals/565825/25/background.png)
EDS84DMOTPNET EN 2.0 - 11/2011
L
25
Communication manual 8400 motec PROFINET
Installation
Electrical installation
5.2.3
External voltage supply
The external voltage supply can be used to establish PROFINET communication for
commissioning and to query the data of the digital and analog inputs.
Furthermore the external voltage supply serves to maintain PROFINET communication
if the main supply fails.
The digital inputs RFR, DI1 ... DI5 and the analog input can continue to be evaluated.
The external voltage supply is done via the terminals 24E and GND of the terminal strip
X3.
Permissible voltage (DC) / max. current:
– U = 24 V DC (20 V - 0 % ... 29 V + 0 %)
– I
max
= 400 mA
Access to parameters of a device that is disconnected from the mains is not possible.
"Inverter Drives 8400 motec" hardware manual
Here you can find detailed information on how to wire the Communication Unit.