EDS84DMOTPNET EN 2.0 - 11/2011

L

81

Communication manual 8400 motec PROFINET

Parameter reference

Parameters relevant for PROFINET communication

C13880

C13881

C13885

Parameter | Name:

C13880 | Reaction on communication failure

Data type: UNSIGNED_8

Index: 10695

d

= 29C7

h

The action set in subcode 1 of the code is carried out when the node recognises that it is no longer in the

"Data_Exchange" status.

• Please also observe the notes provided in code

C13881

.

• A change in the monitoring response becomes effective immediately.
Selection list

0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information

Subcodes

Lenze setting

Info

C13880/1

0: No response

"Watchdog/Data Exchange" monitoring

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13881 | Reaction time delay

Data type: UNSIGNED_16

Index: 10694

d

= 29C6

h

If the "Data_Exchange" status is exited, the response parameterised in

C13880

is activated after the time set here .

• The value "65535" in this code deactivates monitoring.

• A change in the monitoring mode becomes effective immediately.
Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 0 ms

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13885 | Clear process data

Data type: UNSIGNED_8

Index: 10690

d

= 29C2

h

This code is used to set the process data which the I/O device is to process in order to maintain the internal

communication when the PROFINET has exited the "Data_Exchange" status.
Selection list

(Lenze setting printed in bold)

0 Use of last master PDOs
1 PDOs are set to the value'0'

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT