Communication manual 8400 motec PROFINET

Error messages

Possible causes and remedies

70

L

EDS84DMOTPNET EN 2.0 - 11/2011

PROFINET: Internal error [0x01bc6011]

PROFINET: Internal error [0x01bc6100]

PROFINET: Internal error [0x01bc6101]

PROFINET: Invalid parameter set [0x01bc641f]

PROFINET: Error: Lenze setting loaded [0x01bc6420]

PROFINET: Invalid module configuration [0x01bc6430]

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble ; Warning locked … Warning … Information

Cause

Remedy

Device is damaged.

Send device with error description to Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble ; Warning locked … Warning … Information

Cause

Remedy

Device is damaged.

Send device with error description to Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble ; Warning locked … Warning … Information

Cause

Remedy

Device is damaged.

Send device with error description to Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble ; Warning locked … Warning … Information

Cause

Remedy

No active parameter set could be loaded

• Download application again (including module).

• Send device with error description to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Access to parameter set was not possible.

• Download application again (including module).

• Send device with error description to Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble ; Warning locked … Warning … Information

Cause

Remedy

A module or submodule does not comply with the

configuration of the Siemens S7 engineering tool.

Check and correct module configuration.