Communication manual 8400 motec PROFINET

Commissioning

Setting the IP configuration

30

L

EDS84DMOTPNET EN 2.0 - 11/2011

6.4

Setting the IP configuration

The IP configuration is required for addressing the Inverter Drive 8400 motec if

communication between the PC/»Engineer« or the IO controller and the controller is to be

effected via PROFINET. For this, an IP address, subnet mask, and gateway address must be

allocated.
If no PROFINET network or no IO controller is available yet, you have the following options

to allocate the IP address, subnet mask, and gateway address for the Communication Unit:

Settings via the PROFINET configurator of the »Engineer«

( 31)

Setting via codes in the »Engineer«

( 33)

Note!

• If the IP parameters are assigned by the IO controller via PROFINET or the

PROFINET configurator of the »Engineer«, changes will become effective

immediately and are saved with mains failure protection.

• The assignment of invalid combinations of IP address, subnet mask, and

gateway address can have the consequence that no connection to the

PROFINET can be established.

• In the case of impermissible settings, the red LED BE blinks (

LED status

displays

( 64)

), and the error message

PROFINET: Stack init error

[0x01bc6534]

( 72)

is output.