Communication manual 8400 motec PROFINET

Commissioning

Setting the IP configuration

6.4.2

Setting via codes in the »Engineer«

You can also set the IP parameters manually via code in the »Engineer« under the Settings

tab.

The IP parameters are written to codes

C13000

(IP address),

C13001

(subnet mask), and

C13002

(gateway address).

How to activate changed settings in the »Engineer«:

1. Execute device command C00002 = "11: Save all parameter sets".
2. Carry out a "reset node" of the node, or switch the voltage supply of the

Communication Unit off and on again

Decimal representation of the IP parameters
By clicking the [ int ] buttons on the right next to the input fields, the IP parameters are

represented as decimal values.
In the case of the decimal representation, the byte sequence is inverted.
Example: IP address 192.168.0.1

C13000

= 16820416 [00000001.00000000.10101000.11000000

bin

]

Note!

• The IP address must only be allocated manually in the »Engineer« if the

PROFINET network is not actuated on the IO controller yet (IP address was not

allocated by the IO controller yet).

• During the IP parameters are set in the »Engineer«, PROFINET communication

with the IO controller must not take place at the same time.

Byte 3

Byte 2

Byte 1

Byte 0

1

0

168

192

0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 0 1 0 1 0 0 0 1 1 0 0 0 0 0 0