Communication manual 8400 motec PROFINET

Commissioning

Setting the station name

28

L

EDS84DMOTPNET EN 2.0 - 11/2011

6.3

Setting the station name

The station name currently used is shown in code

C13864

.

The station name ...

 is required for unambiguous addressing of the Inverter Drive 8400 motec by the I/O

controller.

 can either be assigned by the I/O controller via PROFINET or set manually in the

»Engineer«.

 has to be allocated in accordance with the PROFINET specification:

– 1 or several labels separated by ".".
– Max. length per label: 63 characters
– Max. total length: 240 characters
– Permissible characters: [a ... z], [0 ... 9], [.], [-]
– Labels must not begin or end with [-].

 Prohibited syntax:

– "n.n.n.n" (n = 0 ... 999)
– "port-xyz" (x, y, z = 0 ... 9)
– "port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)

Note!

• The "Node blinking test" PROFINET function which serves to identify an

accessible device is supported. The red LED BE (

LED status displays

( 64)

)

flickers during execution.

• Operation on the PROFINET requires a valid station name.
• In the case of impermissible settings, the red LED BE blinks (

LED status

displays

( 64)

), and the error message

PROFINET: Stack init error

[0x01bc6534]

( 72)

is output. The Communication Unit then internally

continues to work with the deleted name.

• If the station name is assigned by the IO controller via PROFINET or the

PROFINET configurator of the »Engineer«, changes will be effective

immediately.