11 diagnostics, 1 led status displays, Diagnostics – Lenze E84DGFCR User Manual

Page 64: Led status displays, Led status displays ( 64), Led status, Displays, Is activated, Status displays, Communication manual 8400 motec profinet

Advertising
background image

Communication manual 8400 motec PROFINET

Diagnostics

LED status displays

64

L

EDS84DMOTPNET EN 2.0 - 11/2011

11

Diagnostics

PROFINET communication faults can be diagnosed via the LEDs of the Communication

Unit.
Moreover, the »Engineer« provides diagnostic PROFINET information.

11.1

LED status displays

E84DG056

LED

Colour

Status

Description

Link /

Activity 1

Yellow

off

• No cable is connected to PROFINET port 1.

• No communication

on

A cable is connected to PROFINET port 1.

flickering

Communication at PROFINET port 1 is active.

Link /

Activity 2

Yellow

off

• No cable is connected to PROFINET port 2.

• No communication

on

A cable is connected to PROFINET port 2.

flickering

Communication at PROFINET port 2 is active.

BS

(bus status)

green

off

No communication (the Communication Unit is not active on the

fieldbus or is in the "Init" status).

blinking

Communication active (the Communication Unit is in the

"Data_Exchange" status.)

50 ms

50 ms

200 ms