C13887 | suppress signalling diag. mess. upon, C13899 | station name, C13900 | firmware product type – Lenze E84DGFCR User Manual

Page 82: C13887, C13899, Communication manual 8400 motec profinet

Advertising
background image

Communication manual 8400 motec PROFINET

Parameter reference

Parameters relevant for PROFINET communication

82

L

EDS84DMOTPNET EN 2.0 - 11/2011

C13887

C13899

C13900

Parameter | Name:

C13887 | Suppress signalling diag. mess. upon

Data type: BITFIELD_8

Index: 10688

d

= 29C0

h

This code serves to inhibit the transmission of alarm messages to the IO controller. By this, errors of a specific type

can be systematically suppressed. All errors are furthermore entered in the logbook.

• A change will only become effective immediately if no error number with the error type selected here is pending

in C00165.

Value is bit-coded:

Info

Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13899 | Station name

Data type: VISIBLE_STRING

Index: 10676

d

= 29B4

h

The name with a max. length of 240 characters is distributed to the subindices. The name can be entered starting

with subindex 1. The following unused subindices are not relevant.

• The station name must be assigned in accordance with the PROFINET specification. In the standard setting a

deleted name is displayed. The name is also deleted if the "Reset to factory defaults" command is executed by an

IO supervisor or an I/O controller.

• A change of the station name will only become effective by switching the mains of the controller.



Setting the station name ( 28)

Subcodes

Lenze setting

Info

C13899/1

1st ... 30th character

C13899/2

31th ... 60th character

C13899/3

61th ... 90th character

C13899/4

91th ... 120th character

C13899/5

121th ... 150th character

C13899/6

151th ... 180th character

C13899/7

181th ... 210th character

C13899/8

211th ... 240th character

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13900 | Firmware product type

Data type: VISIBLE_STRING

Index: 10675

d

= 29B3

h

The code contains a string with a length of 8 characters. The identification code "E84DGFCR" is output.

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Advertising