Profinet: data output status bad [0x01bc6503, Profinet: data_exchange status quit [0x01bc6531, Profinet: station name error [0x01bc6532 – Lenze E84DGFCR User Manual

Page 71: Profinet: ip address error [0x01bc6533, Message, 0x01bc6501, 0x01bc6502, 0x01bc6503, 0x01bc6531, 0x01bc6532

Advertising
background image

EDS84DMOTPNET EN 2.0 - 11/2011

L

71

Communication manual 8400 motec PROFINET

Error messages

Possible causes and remedies

PROFINET: Record Parameter: Invalid read [0x01bc6501]

PROFINET: Record Parameter: Invalid write [0x01bc6502]

PROFINET: Data output status bad [0x01bc6503]

PROFINET: Data_Exchange status quit [0x01bc6531]

PROFINET: Station name error [0x01bc6532]

PROFINET: IP address error [0x01bc6533]

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

Invalid parameter read access

Check configuration.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

Invalid parameter write access

When reading back data, the IO controller requested a

too short data length (number of data bytes).

Check configuration.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

• Output data invalid.

• Connection to Siemens S7 has been interrupted.

• Check cables and terminals.

• Connect network cable to PROFINET connections.

Response (Lenze setting printed in bold)

Setting:

C13880/1

(; Adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

The data exchange via PROFINET has been terminated.

• See also chapter "

Interruption of PROFINET

communication

"

( 62)

.

• Check cables and terminals.

• Connect network cable to PROFINET connections.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Station name is not DNS-conform.

Use DNS-conform station name.



Setting the station name ( 28)

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

An invalid IP address has been assigned by the I/O

controller via PROFINET or has been set in code

C13000

.

• Make sure that the I/O controller has assigned a valid

IP address via PROFINET.

• Set a valid IP address.



Setting the IP configuration ( 30)