Communication manual 8400 motec PROFINET

Parameter data transfer

Consistent parameter data

9.5

Consistent parameter data

In the PROFINET communication system, data are permanently exchanged between the

host (CPU + I/O controller) and the standard device via the plugged-on I/O device interface

module. The I/O controller and the CPU (central processing unit) of the host access a joint

memory: the dual port memory (DPM).

 The DPM allows data exchange in both directions (write/read):

It could happen that a slower I/O controller writing would be overtaken by a faster CPU

reading within a cycle time without any further data organisation.
In order to avoid an impermissible status, the transmitted parameter data are to be

marked as "consistent".

Data communication with consistency
With consistency, either "reading" or "writing" is possible when the I/O controller and the

CPU simultaneously access the memory:

 The I/O controller transfers data only as a complete data set.
 The CPU can only access completely updated data sets.
 The I/O controller cannot read or write data as long as the CPU accesses consistent

data.

The result becomes clear from the example below:

1. As the I/O controller can only write when the CPU does not read, the I/O controller has

to wait until the data are completely read by the CPU.

2. The I/O controller only writes a complete data set into the DPM.

Configuring consistent data

Central processing unit

(CPU)

Dual port memory

(DPM)

I/O controller

CPU wants to read.

I/O controller wants to write at the same

time.

Central processing unit

(CPU)

Dual port memory

(DPM)

I/O controller

Note!

Consistency is achieved by an appropriate I/O controller configuration (see

documentation for the configuring software).