Commissioning

Configuring the PROFINET IO controller

6.2

Configuring the PROFINET IO controller

For communication with the PROFINET Communication Unit, the IO controller must be

configured first.

Configuration for device control
For the configuration of PROFINET, the current PROFINET device description file (XML) of

the Communication Unit has to be imported in the IO controller.
The device description file GSDML-Vx.z-Lenze-8440PNabb-yyyymmdd.xml can be found in

the download area at:

www.Lenze.com

Defining the user data length
The user data length is defined during the initialisation phase of the I/O controller.
The PROFINET Communication Unit supports the configuration of max. 8 process data

words (max. 16 bytes).

Description of the device data base file

Example of device data base file selection

 "PCD (8W)" = 8 process data words in slot 1 of the PROFINET telegram

Wildcards in the file name "GSDML-Vx.z-Lenze-8440PN100-yyyymmdd.xml"
x

Main version of the GSDML scheme used

z

Subversion of the GSDML scheme used

A

Major version of the software version

bb

Minor version of the software version

yyyy

Year

mm

Month

dd

Day

Selection text

Process data

Assigned

I/O memory

Slot 1: PCD (nW)

1 ... 8 words

0 ... 16 bytes

Slot 2: AI/DI (nW)

0 ... 2 words

0 ... 4 bytes