Lenze 8615E User Manual

Page 109

Advertising
background image

107

Code

Name

Parameter
(Factory settings are printed in bold)

Acceptance see

page

Your
settings

C119

Preselection:
Monitoring

-0-

Digital input TRIP set

-1-

PTC input

-15-

Inverter overload (I

t monitoring)

-16-

Motor overload (I

2

t monitoring)

SH + PRG

97,
98

C120

Function for
C119

For C119 = -0-. -1-
-0-

Monitoring not active

-1-

Monitoring active, sets TRIP

-2-

Monitoring active, sets warning

For C119 = -15-
-0-

Rated power for temperature range up
to 50°C

-1-

Increased power for temperature
range up to 45°C

-2-

Maximum power for temperature
range up to 40°C

For C119 = -16-
-0-

Monitoring not active

-1-

Monitoring active, sets TRIP

SH + PRG

97,
98

C125*

Baud rate
(only for
LECOM)

-0-

9600 baud

-1-

4800 baud

-2-

2400 baud

-3-

1200 baud

SH + PRG

111

C130

Enable
additional pair
of ramp times
(main set-
value)

-0-

Acceleration and deceleration time
(C012 and C013) active/activate

-1-

Additional pair of ramp times 1
active/activate

-2-

Additional pair of ramp times 2
active/activate

...

...

-15-

Additional pair of ramp times 15
active/activate

SH + PRG

81

C131

Ramp gener.
stop (main set-
value)

-0-

Ramp generator enabled

-1-

Ramp generator stopped

SH + PRG

84

C132

Ramp
generator input
= 0 (main set-
value)

-0-

Ramp generator input enabled

-1-

Ramp generator input = 0/
set to zero

SH + PRG

84

C134

Ramp gener.
characteristic
(main set-
value)

-0-

linear characteristic

-1-

S-shaped characteristic

[SH + PRG] 93

C142*

Flying restart
circuit

-0-

No flying restart

-1-

Flying restart in the selected direction of
rotation

-2-

Flying restart in both directions of rotation

[SH + PRG] 95

C143*

Threshold for
automatic
chopping
frequency
reduction to 2
kHz

0.0Hz

0.0 to 10.0Hz
0.0Hz = automatic chopping frequency
reduction switched off
(in steps of 0.1Hz)

ON-LINE

92

C160*

Display of
process step

-0-

Process step not active /finished

-x-

Process step x is active

94

C161-
C168

Stored fault
indications

Display of stored fault indications, only readable via
LECOM

111,
117

C172*

Set-value input -0-

Set-value 1 (C046) and feedback of PI
controller (C051) as relative value

-1-

Set-value 1 (C046) and feedback of

PI controller (C051) as absolute value

[SH + PRG] 64

C176*

Function
terminals 21,
22

-0-

Terminal 21: Remove quick stop
Terminal 22: Remove quick stop,
invert main set-value

-1-

Terminal 21: Invert main set-value
Terminal 22: Remove quick stop

[SH + PRG] 59

Advertising