Lenze 8615E User Manual

Page 19

Advertising
background image

17

3.2

Applications with high overload,
peak torque up to 170% of the rated motor torque

For applications which require a standard
overload behaviour of an inverter (e.g. general
mechanical engineering, hoists, travelling drives,
calenders).

The inverter provides 150% of the rated torque for
a maximum of 30s.
In the event of cyclic overload, the ratio of overload

time and cycle time must not exceed 0.1.

For this application, the monitoring of the output

current is set to operation with increased power

using the codes C119 and C120 (see page 97).

Please note that a maximum ambient temperature
of 45°C is permissible.

Type

Order no.

Rated

motor

power

kW

Rated

output

current

A

max.

output

current

A for 30s

Output power

kVA

400V 50Hz 480V 60Hz

Mains

current

A

Power

loss

W

8601

33.8601_E

1.5

4.0

6.0

2.77

3.33

4.0

140

8602

33.8602_E

2.2

5.3

7.8

3.67

4.41

5.3

155

8603

33.8603_E

3.0

7.4

11.0

5.13

6.15

7.4

180

8604

33.8604_E

4.0

10.1

15.0

7.0

8.4

9.4

210

8605

33.8605_E

5.5

12.7

19.0

8.8

10.6

11.8

235

8606

33.8606_E

7.5

17.6

26.0

12.2

14.6

16.3

290

8607

33.8607_E

11.0

22.7

33.0

15.7

18.9

20.7

340

8608

33.8608_E

15.0

31.7

47.0

22.0

26.3

28.0

440

8609

33.8609_E

18.5

43.2

64.0

29.9

35.9

38.0

560

8610

33.8610_E

22.0

53.3

79.0

36.9

44.3

47.0

670

8611

33.8611_E

30.0

63.5

94.0

44.0

52.8

55.0

775

8612

33.8612_E

37.0

81.0

120.0

56.1

67.3

71.0

960

8613

33.8613_E

45.0

101.0

150.0

70.0

84.0

84.0

1175

8614

33.8614_E

55.0

120.0

178.0

83.1

99.8

105.0

1375

8615

33.8615_E

75.0

148.0

220.0

103.0

123.0

129.0

1675