3.7.1 V/f characteristic control

You have to change from I

0

control (factory setting) to V/f

characteristic control if you want to supply several drives with
different loads or rated power from one inverter. Also for pump and
blower drives to be operated with a square characteristic, a V/f
characteristic control is required.

V/f characteristic
With V/f characteristic control the output voltage is controlled
according to the characteristic set via C014 and C016.

Via code C014 you can determine whether the characteristic
should have a linear or a square shape.

1

0

0

V

400V

1

fd

fdN

Vmin

rated point

1

0

0

V

400V

1

fd

fdN

Vmin

rated point

linear characteristic square characteristic

The square characteristic can be used for pump and blower drives
or comparable applications.

V/f rated frequency
With the V/f rated frequency, the slope of the characteristic is set.
The value to be entered under C015 results from the motor ratings:

V f rated frequency

V

V

rated motor frequency

Nmotor

/

=

400

The values for the most common motor types can be obtained from
the following table.

Motor data

V/f rated

rated voltage

rated frequency

frequency (C015)

380V

50Hz

52.6Hz

400V

50Hz

50.0Hz

415V

50Hz

48.2Hz

415V

60Hz

57.8Hz

440V

60Hz

54.5Hz

460V

60Hz

52.2Hz

480V

50Hz

41.7Hz

480V

60Hz

50.0Hz