Voltage boost V

min

In the low speed range, the obtained torque is determined largely
by the set voltage boost. If you set V

min

(C016), make sure that the

motor cannot be destroyed by overheat.

Experience tells that self-ventilated standard asynchronous
machines of insulation class B can be operated in a frequency
range up to 25Hz only for a short time with rated current. Therefore
proceed as follows:

The motor should be operated in idle running.

Provide a set-value of 4 to 5 Hz.

The voltage boost should be set such that

the motor current (C054) does not exceed the rated value
for short-time operation in the low frequency range.

the motor current (C054) does not exceed 80 % of its rated
value for permanent operation in the low frequency range.

For exact data of the permissible motor current please refer to the
motor manufacturer.

Forced-ventilated machines can be permanently operated with
rated current even in the low frequency range.

Code

Parameter

Meaning

Acceptance

C014

-0-
-1-

linear characteristic
square characteristic

[SH + PRG]

C015

50.0Hz
7.5...960Hz

V/f rated frequency

ON-LINE

C016

0.0%
0.0...40%

voltage boost

ON-LINE