List of fault indications

Display on
keypad

Display on
host

Fault

Cause

Remedy

---

0

no fault

OC1

11

Short circuit/
˝Earth fault

Short circuit/earth fault at the
motor side e.g. by
- defective motor cable
- contact of motor windings
- contact between motor
housing and winding

Check motor cable for short-
circuit
Separate motor cable from
inverter and check insulation
between U-V-W and PE
Check motor

OC5

15

Inverter
overload

Frequent or too long
accelerations with overcurrent
Permanent overload with motor
current > 110% rated current.

The permissible output power
was reduced to 12 or 16 kHz by
increasing the chopping
frequency

Check dimensioning of the drive
If necessary, set I

t monitoring

(C119, C120) to increased or
maximum permanent power
(observe ambient temperature)
Check setting of the chopping
frequency (C018)

OC6

16

Motor overload Thermal overlaod of the motor,

caused by e.g.
- non-permissible continuous
current
- frequent or too long
accelerations

Check dimensioning of the drive
Enter correct motor size (C086),
if necessary, switch off
monitoring (C119, C120)

OH

50

Overheat
heatsink

Heatsink too hot, e.g. because,

- Ambient temperature too high
- Heatsink strongly polluted
- Incorrect mounting

Allow inverter to cool and
ensure a better ventilation
- Check ambient temperature in
the control cabinet
- Clean heatsink
- Change mounting

OH3

53

Overheat PTC
input

Motor is overheated
PTC connecting cable
interrupted
PTC input open

Check dimensioning of the drive
Check PTC connection

Bridge PTC input

CEO

61

Communication
error 0

Supply of automation module
switched off or defective
Connection to automation
module interrupted

Check supply

Check connecting cable

U15

70

±

15-V supply

defective

Overload/Short-circuit at
terminal 20

±

15-V supply defective

Check load at terminal 20

Return inverter to factory

CCr

71

System failure

Strong interferences on control
cables
PE loops in the wiring

Screen control cables

Check PE wiring and GND

Pr

72

Parameter
reset

After mains connection a
modified software version was
found.
Factory settings were loaded
automatically.

Set desired parameters and
save under C003.

Pr1...Pr4

72

Parameter
reset

When parameter sets 1 to 4
were loaded, a fault was found.
Factory settings were loaded
automatically.

Set desired parameters and
save under C003.

PEr

74

Program error

Contact factory

EER

91

External fault

Signal via digital input "fault
indication"
Incorrect programming of the
input "fault indication"

Check external feedback source

Check programming of the input
"fault indication"